Innovenergy_trunk/doc/controller_tests/Limit Charge Power -> Optim...

21 lines
628 B
Markdown
Raw Normal View History

2023-02-16 12:57:06 +00:00
<br>
# Limit Charge Power -> Optimize Self-Consumption
Initial State: `Limit Charge Power`
Target State: `Optimize Self-Consumption`
## Test Procedure
1. `Grid setpoint` is set to 2500W.
2. The system is brought to the `Limit Charge Power` by activating its option and the `Maximum Charge Power` is set to 1000W.
3. A load of 2000W or more is connected to the system.
## Expected Outcome
As soon as the load is connected, the battery state changes into the `Optimize Self-Consumption` state and charges with power of range (0W-1000W), depending
on the load power.
## Tested Outcome
The systen reacted as expected.