Update the discharginglimit calculation
This commit is contained in:
parent
cd73ab0986
commit
f8db3ebb56
|
@ -215,7 +215,7 @@ internal static class Program
|
|||
//foreach (var batteryNodeRecord in record.Battery.Devices)
|
||||
//{
|
||||
// var ioStates = batteryNodeRecord.IoStates;
|
||||
|
||||
//
|
||||
// batteryNodeRecord.FwVersion.WriteLine(" FwVersion ");
|
||||
// batteryNodeRecord.IoStatus.ConnectedToDcBus.WriteLine(" ConnectedToDcBus");
|
||||
// batteryNodeRecord.IoStatus.AlarmOutActive.WriteLine(" AlarmOutActive");
|
||||
|
@ -239,14 +239,14 @@ internal static class Program
|
|||
// ("********************************************************").WriteLine();
|
||||
//}
|
||||
|
||||
//record.GridMeter?.ActivePowerExportT1.WriteLine("kWh Export 5910");
|
||||
//record.GridMeter?.ActivePowerImportT1.WriteLine("kWh Import 5902");
|
||||
//record.GridMeter?.ActivePowerExportT2.WriteLine("Wh Export 6008");
|
||||
//record.GridMeter?.ActivePowerImportT2.WriteLine("Wh Import 6028");
|
||||
//record.GridMeter?.ActivePowerExportT3.WriteLine("Kwh Import 8004");
|
||||
//record.GridMeter?.ActivePowerImportT3.WriteLine("kWh Export 8014");
|
||||
//record.GridMeter?.ActivePowerExportT4.WriteLine("port 5906");
|
||||
//record.GridMeter?.ActivePowerImportT4.WriteLine("port 5914");
|
||||
//record.GridMeter?.ActivePowerImportT1.WriteLine("kWh Export 6004");
|
||||
//record.GridMeter?.ActivePowerExportT1.WriteLine("kWh Import 6024");
|
||||
//record.GridMeter?.ActivePowerImportT2.WriteLine("Wh Import 6008");
|
||||
//record.GridMeter?.ActivePowerExportT2.WriteLine("Wh Export 6028");
|
||||
//record.GridMeter?.ActivePowerExportT3.WriteLine("KWh Export 8012");
|
||||
//record.GridMeter?.ActivePowerImportT3.WriteLine("kWh Import 8002");
|
||||
//record.GridMeter?.ActivePowerImportT4.WriteLine("Wh Import 8000");
|
||||
//record.GridMeter?.ActivePowerExportT4.WriteLine("Wh Export 8010");
|
||||
|
||||
var currentSalimaxState = GetSalimaxStateAlarm(record);
|
||||
|
||||
|
@ -424,8 +424,10 @@ internal static class Program
|
|||
CreatedBy = "Battery node" + record.Config.Devices.BatteryNodes[i],
|
||||
Description = alarm
|
||||
});
|
||||
i++;
|
||||
}
|
||||
|
||||
i++;
|
||||
|
||||
}
|
||||
|
||||
}
|
||||
|
@ -452,33 +454,11 @@ internal static class Program
|
|||
});
|
||||
}
|
||||
|
||||
if (record.Battery != null)
|
||||
{
|
||||
var i = 0;
|
||||
foreach (var warning in record.Battery.Warnings)
|
||||
{
|
||||
warningList.Add(new AlarmOrWarning
|
||||
{
|
||||
Date = DateTime.Now.ToString("yyyy-MM-dd"),
|
||||
Time = DateTime.Now.ToString("HH:mm:ss"),
|
||||
CreatedBy = "Battery node" + record.Config.Devices.BatteryNodes[i],
|
||||
Description = warning
|
||||
});
|
||||
}
|
||||
}
|
||||
|
||||
var salimaxAlarmsState = (record.Battery is not null && record.Battery.Warnings.Any())
|
||||
| record.AcDc.Warnings.Any()
|
||||
| record.AcDc.SystemControl.Warnings.Any()
|
||||
| record.DcDc.Warnings.Any()
|
||||
var salimaxAlarmsState = warningList.Any()
|
||||
? SalimaxAlarmState.Orange
|
||||
: SalimaxAlarmState.Green; // this will be replaced by LedState
|
||||
|
||||
salimaxAlarmsState = (record.Battery is not null && record.Battery.Alarms.Any())
|
||||
| record.AcDc.Alarms.Any()
|
||||
| record.AcDc.SystemControl.Alarms.Any()
|
||||
| record.DcDc.Alarms.Any()
|
||||
| alarmCondition is not null
|
||||
salimaxAlarmsState = alarmList.Any()
|
||||
? SalimaxAlarmState.Red
|
||||
: salimaxAlarmsState; // this will be replaced by LedState
|
||||
|
||||
|
@ -524,8 +504,8 @@ internal static class Program
|
|||
if (r.Battery != null)
|
||||
{
|
||||
const Int32 stringsByBattery = 5;
|
||||
var numberOfBatteries = r.Battery.Devices.Count;
|
||||
var numberOfTotalStrings = stringsByBattery * numberOfBatteries;
|
||||
var numberOfBatteriesConfigured = r.Config.Devices.BatteryNodes.Length;
|
||||
var numberOfTotalStrings = stringsByBattery * numberOfBatteriesConfigured;
|
||||
var dischargingCurrentByString = configFile.MaxBatteryDischargingCurrent / numberOfTotalStrings;
|
||||
|
||||
var boolList = new List<Boolean>();
|
||||
|
@ -539,7 +519,7 @@ internal static class Program
|
|||
boolList.Add(stringActive.String5Active);
|
||||
}
|
||||
|
||||
var numberOfBatteriesStringActive = boolList.Count(_ => true);
|
||||
var numberOfBatteriesStringActive = boolList.Count(b => b);
|
||||
|
||||
if (numberOfTotalStrings != 0)
|
||||
{
|
||||
|
@ -552,7 +532,7 @@ internal static class Program
|
|||
//maxBatteryDischargingCurrentLive.WriteLine(" maxBatteryDischargingCurrentLive");
|
||||
}
|
||||
|
||||
// TODO The discharging current is well calculated but not communicated to live. Need to think about this
|
||||
// TODO The discharging current is well calculated but not communicated to live. But Written in S3
|
||||
|
||||
var devicesConfig = r.AcDc.Devices.All(d => d.Control.Ac.GridType == GridType.GridTied400V50Hz) ? configFile.GridTie : configFile.IslandMode; // TODO if any of the grid tie mode
|
||||
|
||||
|
@ -578,28 +558,31 @@ internal static class Program
|
|||
r.AcDc.ResetAlarms();
|
||||
}
|
||||
|
||||
// This is will be used for provider throttling
|
||||
// This is will be used for provider throttling, this example is only for either 100% or 0 %
|
||||
private static void ControlPvPower(this StatusRecord r, Int16 exportLimit = 100)
|
||||
{
|
||||
|
||||
// 950 V = 0%
|
||||
// 750 V = 100%
|
||||
|
||||
const Int32 maxDcLinkVoltage = 950;
|
||||
const Int32 minDcLinkVoltage = 850; // we may dont need this two;
|
||||
const Int32 referenceDcLinkVoltage = 900; // we may dont need this two;
|
||||
|
||||
var inverters = r.AcDc.Devices;
|
||||
var dcDevices = r.DcDc.Devices;
|
||||
var configFile = r.Config;
|
||||
|
||||
inverters.ForEach(d => d.Control.Dc.MaxVoltage = maxDcLinkVoltage);
|
||||
inverters.ForEach(d => d.Control.Dc.MinVoltage = minDcLinkVoltage);
|
||||
inverters.ForEach(d => d.Control.Dc.ReferenceVoltage = referenceDcLinkVoltage);
|
||||
var devicesConfig = r.AcDc.Devices.All(d => d.Control.Ac.GridType == GridType.GridTied400V50Hz) ? configFile.GridTie : configFile.IslandMode; // TODO if any of the grid tie mode
|
||||
|
||||
dcDevices.ForEach(d => d.Control.DroopControl.UpperVoltage = maxDcLinkVoltage);
|
||||
dcDevices.ForEach(d => d.Control.DroopControl.LowerVoltage = minDcLinkVoltage);
|
||||
dcDevices.ForEach(d => d.Control.DroopControl.ReferenceVoltage = referenceDcLinkVoltage);
|
||||
// 950 V = 0%
|
||||
// 750 V = 100%
|
||||
|
||||
const Int32 maxDcLinkVoltage = 950;
|
||||
const Int32 minDcLinkVoltage = 850; // we may dont need this;
|
||||
const Int32 referenceDcLinkVoltage = 900; // we may dont need this;
|
||||
|
||||
|
||||
inverters.ForEach(d => d.Control.Dc.MaxVoltage = exportLimit == 100 ? devicesConfig.AcDc.MaxDcLinkVoltage : maxDcLinkVoltage);
|
||||
inverters.ForEach(d => d.Control.Dc.MinVoltage = exportLimit == 100 ? devicesConfig.AcDc.MinDcLinkVoltage : minDcLinkVoltage);
|
||||
inverters.ForEach(d => d.Control.Dc.ReferenceVoltage = exportLimit == 100 ? devicesConfig.AcDc.ReferenceDcLinkVoltage : referenceDcLinkVoltage);
|
||||
|
||||
dcDevices.ForEach(d => d.Control.DroopControl.UpperVoltage = exportLimit == 100 ? devicesConfig.DcDc.UpperDcLinkVoltage : maxDcLinkVoltage);
|
||||
dcDevices.ForEach(d => d.Control.DroopControl.LowerVoltage = exportLimit == 100 ? devicesConfig.DcDc.LowerDcLinkVoltage : minDcLinkVoltage);
|
||||
dcDevices.ForEach(d => d.Control.DroopControl.ReferenceVoltage = exportLimit == 100 ? devicesConfig.DcDc.ReferenceDcLinkVoltage : referenceDcLinkVoltage);
|
||||
}
|
||||
|
||||
// why this is not in Controller?
|
||||
|
@ -687,6 +670,11 @@ internal static class Program
|
|||
return true;
|
||||
}
|
||||
|
||||
private static Boolean IsPowerOfTwo(Int32 n)
|
||||
{
|
||||
return n > 0 && (n & (n - 1)) == 0;
|
||||
}
|
||||
|
||||
private static void ApplyConfigFile(this StatusRecord status, Configuration? config)
|
||||
{
|
||||
status.Config.MinSoc = config.MinimumSoC;
|
||||
|
|
Loading…