# Hold min SOC -> Optimize Self-Consumption Initial State: `Hold min SOC` Target State: `Optimize Self-Consumption` ## Test Procedure 1. `Min SOC` is set to slightly lower than the current SOC 2. `Min SOC` should be 50% or lower 3. `Grid setpoint` is set to a negative value -2000W 4. Wait until the system reaches the `Hold min SOC` state and discharging power falls below 1500W 5. `Grid setpoint` is set to a positive value: 2000W ## Expected Outcome The system first settles into the `Hold min SOC` state. As soon as the `Grid setpoint` is set to positive, the system changes into the `Optimize Self-Consumption` and charges with ~2000W. ## Tested Outcome While the system was on `Hold min SOC` state sitting on around 46% SOC, the `Grid setpoint` was set to a 2000W, the system started charging with a power of around 1600W until around 70% SOC, then it started throtteling the charging power. ![Hold min SOC -> Optimize Self-Consumption](Test9.png)