# Hold min SOC -> Forced EOC Initial State: `Hold min SOC` Target State: `Forced EOC` ## Test Procedure 1. `Min SOC` is set lower than the current SOC 2. `Min SOC` should be 50% or lower 3. `Grid setpoint` is set to a negative value (-2000W) 4. Wait until the system reaches the `Hold min SOC` state 5. activate `Force charge now` on the remote console ## Expected Outcome As soon as `Force charge now` is activated, the system changes into the `Forced EOC` state and charges with high power (min. 1000W) ## Tested Outcome The system reacted as expected and switched from `Hold min SOC` state to `Forced EOC` state when `Force charge now` was activated on the remote console. The charging power was around 1200W. The were observed power drops during this process. ![Hold min SOC -> Forced EOC](Test6.png)