# Limit Charge Power -> Optimize Self-Consumption Initial State: `Limit Charge Power` Target State: `Optimize Self-Consumption` ## Test Procedure 1. `Grid setpoint` is set to 2500W. 2. The system is brought to the `Limit Charge Power` by activating its option and the `Maximum Charge Power` is set to 1000W. 3. A load of 2000W or more is connected to the system. ## Expected Outcome As soon as the load is connected, the battery state changes into the `Optimize Self-Consumption` state and charges with power of range (0W-1000W), depending on the load power. ## Tested Outcome The systen reacted as expected.