# Charge to min SOC -> Forced EOC

Initial State: `Charge to min SOC`  
Target State:  `Forced EOC`  

## Test Procedure

1. The system is put into the `Charge to min SOC` state by manually setting the `Min SOC` higher than the current `SOC`. 
2. `Force charge now` is activated on the remote console

## Expected Outcome

Any one of the below:

- The system immediately switches to the `Forced EOC` state
- The system remains in `Charge to min SOC` until it reaches the `Min SOC`, and then switches to the `Forced EOC` state

## Tested Outcome

The system reacted as expected from the second situation and continues the `Charge to min SOC` until it reaches the  
`Min SOC`, and then switches to the `Forced EOC` state continuing the same charging pattern, by charging as fast as  
possible till reaching the fully charged state.

![Forced EOC](Test1.png)