<br>
# Hold min SOC -> Forced EOC

Initial State: `Hold min SOC`  
Target State:  `Forced EOC`  

## Test Procedure

1. `Min SOC` is set lower than the current SOC
2. `Min SOC` should be 50% or lower
3. `Grid setpoint` is set to a negative value (-2000W)
4. Wait until the system reaches the `Hold min SOC` state
5. activate `Force charge now` on the remote console

## Expected Outcome

As soon as `Force charge now` is activated, the system changes into the `Forced EOC` state and charges with high power (min. 1000W)

## Tested Outcome

The system reacted as expected and switched from `Hold min SOC` state to `Forced EOC` state when `Force charge now` was activated on the  
remote console. The charging power was around 1200W. The were observed power drops during this process. 

![Hold min SOC -> Forced EOC](Test6.png)