# Charge to min SOC -> Forced EOC Initial State: `Charge to min SOC` Target State: `Forced EOC` ## Test Procedure 1. The system is put into the `Charge to min SOC` state by manually setting the `Min SOC` higher than the current `SOC`. 2. `Force charge now` is activated on the remote console ## Expected Outcome Any one of the below: - The system immediately switches to the `Forced EOC` state - The system remains in `Charge to min SOC` until it reaches the `Min SOC`, and then switches to the `Forced EOC` state ## Tested Outcome The system reacted as expected from the second situation and continues the `Charge to min SOC` until it reaches the `Min SOC`, and then switches to the `Forced EOC` state continuing the same charging pattern, by charging as fast as possible till reaching the fully charged state. ![Forced EOC](Test1.png)