Innovenergy_trunk/doc/controller_tests/Forced EOC -> Optimize Self...

31 lines
1.2 KiB
Markdown

<br>
# Forced EOC -> Optimize Self-Consumption (charging)
Initial State: `Forced EOC`
Target State: `Optimize Self-Consumption`
## Test Procedure
1. `SOC` should be 98% or below
2. A production surplus is simulated by setting the `Grid setpoint` to a positive value: 2000W
3. The system is brought to the `Forced EOC` state using `Force charge now` in the gui.
4. Wait until the system changes to `Optimize Self-Consumption`
## Expected Outcome
- The system charges the battery to EOC in the `Forced EOC` state.
- charging power decreases as SOC approaches 100%
- the system changes into `Optimize Self-Consumption`
- the system continues to charge with very low power <100W or discharges with very low power <100W
- `Time to forced full charge` displayed on the gui is 6d 18h +-1h
## Tested Outcome
The system reacted as expected and switched to `Optimize Self-Consumption` when the battery is fully charged and having
100% SOC. The system is continuously charging with a power of ~3W. `Time to forced full charge` is correctly displayed and
gets restarted or stays the same (6d 18h) as long as the battery is in charge mode.
![Charge to mind SOC -> Optimize Self-Consumption](Test7.png)