Innovenergy_trunk/doc/controller_tests/Forced EOC -> Optimize Self...

1.0 KiB


# Forced EOC -> Optimize Self-Consumption (discharging)

Initial State: Forced EOC
Target State: Optimize Self-Consumption

Test Procedure

  1. SOC should be 98% or below
  2. A production deficit is simulated by setting the Grid setpoint to a negative value: -2000W
  3. The system is brought to the Forced EOC state using Force charge now in the gui.
  4. Wait until the system changes to Optimize Self-Consumption

Expected Outcome

  • The system charges the battery to EOC in the Forced EOC state.
  • charging power decreases as SOC approaches 100%
  • the system changes into Optimize Self-Consumption
  • the system discharges with 2000W +-100W
  • Time to forced full charge displayed on the gui 6d 18h +-1h

Tested Outcome

The system reacted as expected and switched to Optimize Self-Consumption when the battery is fully charged and having
100% SOC. The system is excessively discharging with a power of ~2350W. Time to forced full charge is correctly displayed.

Charge to mind SOC -> Optimize Self-Consumption