Innovenergy_trunk/doc/controller_tests/Forced EOC -> Optimize Self...

30 lines
1.0 KiB
Markdown

<br>
# Forced EOC -> Optimize Self-Consumption (discharging)
Initial State: `Forced EOC`
Target State: `Optimize Self-Consumption`
## Test Procedure
1. `SOC` should be 98% or below
2. A production deficit is simulated by setting the `Grid setpoint` to a negative value: -2000W
3. The system is brought to the `Forced EOC` state using `Force charge now` in the gui.
4. Wait until the system changes to `Optimize Self-Consumption`
## Expected Outcome
- The system charges the battery to EOC in the `Forced EOC` state.
- charging power decreases as SOC approaches 100%
- the system changes into `Optimize Self-Consumption`
- the system discharges with 2000W +-100W
- `Time to forced full charge` displayed on the gui `6d 18h` +-1h
## Tested Outcome
The system reacted as expected and switched to `Optimize Self-Consumption` when the battery is fully charged and having
100% SOC. The system is excessively discharging with a power of ~2350W. `Time to forced full charge` is correctly displayed.
![Charge to mind SOC -> Optimize Self-Consumption](Test8.png)