# Optimize Self-Consumption -> Limit Discharge Power

Initial State: Optimize Self-Consumption
Target State: Limit Discharge Power

Test Procedure

  1. The system is brought to the Optimize Self-Consumption state by setting Min SOC lower than the current SOC.
  2. Grid setpoint is set to 0W.
  3. The Limit Discharge Power option is activated and the Maximum Discharge Power is set to 1000W.
  4. A load of 2000W or more is connected to the system.

Expected Outcome

As soon as the load is connected, the battery state changes into the Limit Discharge Power state and discharges with a maximum power of 1000W(+/-50W).
The rest of the load is supplied by the grid.

Tested Outcome

The systen reacted as expected.