# Hold min SOC -> Optimize Self-Consumption
Initial State: Hold min SOC
Target State: Optimize Self-Consumption
Test Procedure
Min SOC
is set to slightly lower than the current SOCMin SOC
should be 50% or lowerGrid setpoint
is set to a negative value -2000W- Wait until the system reaches the
Hold min SOC
state and discharging power falls below 1500W Grid setpoint
is set to a positive value: 2000W
Expected Outcome
The system first settles into the Hold min SOC
state.
As soon as the Grid setpoint
is set to positive, the system changes into the Optimize Self-Consumption
and
charges with ~2000W.
Tested Outcome
While the system was on Hold min SOC
state sitting on around 46% SOC, the Grid setpoint
was set to a 2000W, the system
started charging with a power of around 1600W until around 70% SOC, then it started throtteling the charging power.