31 lines
1.2 KiB
Markdown
31 lines
1.2 KiB
Markdown
<br>
|
|
# Forced EOC -> Optimize Self-Consumption (charging)
|
|
|
|
Initial State: `Forced EOC`
|
|
Target State: `Optimize Self-Consumption`
|
|
|
|
## Test Procedure
|
|
|
|
1. `SOC` should be 98% or below
|
|
2. A production surplus is simulated by setting the `Grid setpoint` to a positive value: 2000W
|
|
3. The system is brought to the `Forced EOC` state using `Force charge now` in the gui.
|
|
4. Wait until the system changes to `Optimize Self-Consumption`
|
|
|
|
## Expected Outcome
|
|
|
|
- The system charges the battery to EOC in the `Forced EOC` state.
|
|
- charging power decreases as SOC approaches 100%
|
|
- the system changes into `Optimize Self-Consumption`
|
|
- the system continues to charge with very low power <100W or discharges with very low power <100W
|
|
- `Time to forced full charge` displayed on the gui is 6d 18h +-1h
|
|
|
|
## Tested Outcome
|
|
|
|
The system reacted as expected and switched to `Optimize Self-Consumption` when the battery is fully charged and having
|
|
100% SOC. The system is continuously charging with a power of ~3W. `Time to forced full charge` is correctly displayed and
|
|
gets restarted or stays the same (6d 18h) as long as the battery is in charge mode.
|
|
|
|
![Charge to mind SOC -> Optimize Self-Consumption](Test7.png)
|
|
|
|
|