# Optimize Self-Consumption -> Limit Discharge Power
|
|
|
|
Initial State: `Optimize Self-Consumption`
|
|
Target State: `Limit Discharge Power`
|
|
|
|
## Test Procedure
|
|
|
|
1. The system is brought to the `Optimize Self-Consumption` state by setting `Min SOC` lower than the current SOC.
|
|
2. `Grid setpoint` is set to 0W.
|
|
3. The `Limit Discharge Power` option is activated and the `Maximum Discharge Power` is set to 1000W.
|
|
4. A load of 2000W or more is connected to the system.
|
|
|
|
## Expected Outcome
|
|
|
|
As soon as the load is connected, the battery state changes into the `Limit Discharge Power` state and discharges with a maximum power of 1000W(+/-50W).
|
|
The rest of the load is supplied by the grid.
|
|
|
|
## Tested Outcome
|
|
|
|
The systen reacted as expected.
|