1.1 KiB
1.1 KiB
# Charge to min SOC -> Optimize Self-Consumption
Initial State: Charge to min SOC
Target State: Optimize Self-Consumption
Test Procedure
- The battery is discharged below 20% SOC
Min SOC
is set to 20%- A production surplus is simulated by setting the
Grid setpoint
to a positive value (1200W) - Wait until the
SOC
exceeds 22%
Expected Outcome
The system assumes the Charge to min SOC
state and charges with high power (~2000W), until it reaches Min SOC
.
Once it reaches Min SOC
it does the following:
- it changes into the
Optimize Self-Consumption
state - it continues to charge the battery with an average of 1200W
- charging power does not fluctuate by more than 250W once it has stabilized
Tested Outcome
The system reacted as exactly as expected and switched to Charge to min SOC
and charged as fast as possible till reaching the Min SOC
.
Once the Min SOC
is reached, the battery switches to Optimize Self-Consumption
, where the charging power fluctuations don't exceed 200w.