# Hold min SOC -> Forced EOC
|
|
|
|
Initial State: `Hold min SOC`
|
|
Target State: `Forced EOC`
|
|
|
|
## Test Procedure
|
|
|
|
1. `Min SOC` is set lower than the current SOC
|
|
2. `Min SOC` should be 50% or lower
|
|
3. `Grid setpoint` is set to a negative value (-2000W)
|
|
4. Wait until the system reaches the `Hold min SOC` state
|
|
5. activate `Force charge now` on the remote console
|
|
|
|
## Expected Outcome
|
|
|
|
As soon as `Force charge now` is activated, the system changes into the `Forced EOC` state and charges with high power (min. 1000W)
|
|
|
|
## Tested Outcome
|
|
|
|
The system reacted as expected and switched from `Hold min SOC` state to `Forced EOC` state when `Force charge now` was activated on the
|
|
remote console. The charging power was around 1200W. The were observed power drops during this process.
|
|
|
|
![Hold min SOC -> Forced EOC](Test6.png)
|