# Limit Charge Power -> Optimize Self-Consumption
|
|
|
|
Initial State: `Limit Charge Power`
|
|
Target State: `Optimize Self-Consumption`
|
|
|
|
## Test Procedure
|
|
|
|
1. `Grid setpoint` is set to 2500W.
|
|
2. The system is brought to the `Limit Charge Power` by activating its option and the `Maximum Charge Power` is set to 1000W.
|
|
3. A load of 2000W or more is connected to the system.
|
|
|
|
## Expected Outcome
|
|
|
|
As soon as the load is connected, the battery state changes into the `Optimize Self-Consumption` state and charges with power of range (0W-1000W), depending
|
|
on the load power.
|
|
|
|
## Tested Outcome
|
|
|
|
The systen reacted as expected.
|