# Charge to min SOC -> Hold min SOC
Initial State: Charge to min SOC
Target State: Hold min SOC
Test Procedure
- The battery is discharged below 20% SOC
Min SOC
is set to 20%- A production deficit is simulated by setting
Grid setpoint
to a negative value (-2000W) - Wait until the
SOC
stabilizes slightly aboveMin SOC
Expected Outcome
The system assumes the Charge to min SOC
state and charges with high power (~2000W), until it reaches Min SOC
.
Once it reaches Min SOC
it does the following:
- it changes into the
Hold min SOC
state - the
SOC
stabilizes between 20% and 20.5% - the
SOC
does not fluctuate by more than 0.1% once it has stabilized - charging power does not fluctuate by more than 250W once it has stabilized
Tested Outcome
The system reacted as expected and switched to Charge to min SOC
and charged as fast as possible till reaching the Min SOC
.
Once the Min SOC
is reached, the battery switches to Hold min SOC
, entering a stabilisation state for around 10 minutes where
the charging power remains positive and up to 270 W. After approximately 10 minutes, the battery reaches the final stabilised
state where the charging power fluctuates in range of +-75W. The SOC
fluctuates between 20% and 21%, slighty favouring the later.