1.5 KiB
1.5 KiB
# Optimize Self-Consumption -> Hold min SOC
Initial State: Optimize Self-Consumption
Target State: Hold min SOC
Test Procedure
- The system is brought to the
Optimize Self-Consumption
state by settingMin SOC
lower than the current SOC (min. 5% lower) Min SOC
should not be lower than 10%- A production deficit is simulated by setting
Grid setpoint
to a negative value (-2000W) - Wait until the
SOC
stabilizes slightly aboveMin SOC
Expected Outcome
- The system first discharges the battery with 2000W.
- Somewhere between
Min SOC + 1%
andMin SOC + 4%
the system changes into theHold min SOC
state. - Once in this state, discharging is continuously throttled until it reaches 0W somewhere between
Min SOC + 0.1 %
andMin SOC + 0.5 %
- The system then starts to charge with low power (<300W) in order to compensate for thermal energy loss.
- The
SOC
stabilizes betweenMin SOC
andMin SOC + 0.5 %
- The
SOC
does not fluctuate by more than 0.1% once it has stabilized - Charging power does not fluctuate by more than 250W once it has stabilized
Tested Outcome
The system reacted as expected and switched to Hold min SOC
state once the SOC reached Min SOC + 4%
. Once the state changed to
Hold min SOC
, the discharging power is throttled for around 40 minutes, where it then reached 0W at Min SOC + 1 %
. When stabilized