# Optimize Self-Consumption -> Forced EOC
Initial State: Optimize Self-Consumption
Target State: Forced EOC
Test Procedure
- The system is brought to the
Optimize Self-Consumption
state by settingMin SOC
lower than the current SOC Min SOC
should be 50% or lowerForce charge now
is activated on the remote console
Expected Outcome
As soon as Force charge now
is activated, the system changes into the Forced EOC
state and charges with high power (min. 1000W)
Tested Outcome
The system reacted exactly as expected and switched to Forced EOC
state and charged with higher an average power of around 1200w.