# Charge to min SOC -> Forced EOC

Initial State: Charge to min SOC
Target State: Forced EOC

Test Procedure

  1. The system is put into the Charge to min SOC state by manually setting the Min SOC higher than the current SOC.
  2. Force charge now is activated on the remote console

Expected Outcome

Any one of the below:

  • The system immediately switches to the Forced EOC state
  • The system remains in Charge to min SOC until it reaches the Min SOC, and then switches to the Forced EOC state

Tested Outcome

The system reacted as expected from the second situation and continues the Charge to min SOC until it reaches the
Min SOC, and then switches to the Forced EOC state continuing the same charging pattern, by charging as fast as
possible till reaching the fully charged state.

Forced EOC