# Release 2.60~ie
Remote Console
Battery
menu
- added
Warnings
submenu that shows any active warning of all connected batteries in human readable form along with the technical mnenonic used by FzSonick - added indicator of the number of all active warnings of each individual battery on the submenu label
- added
Alarms
submenu that shows any active alarm of all connected batteries in human readable form along with the technical mnenonic used by FzSonick - added indicator of the number of all active alarms of each individual battery on the submenu label
- added
Individual Batteries
submenu that lists all connected batteries, their node Id and their BMS version - added submenu for each individual battery, showing warnings, alarms, and all other stats for the each specific battery alone.
Settings
menu
- removed
ESS
submenu
InnovEnergy
menu
- added
Charging Strategy
submenu - added
Relay 2
submenu
Charging Strategy
menu
- added
Charging State
indicator - added
Time to forced full charge
indicator - added
Force charge now
button, ability manually to force a full charge - moved the following settings from the
ESS
menu:Grid setpoint
Minimum SOC (unless grid fails)
Grid meter installed
Inverter AC output in use
Fronius Zero feed-in
Fronius Zero feed-in active
Limit the charge power
Maximum charge power
Limit the discharge power
Maximum discharge power
Scheduled charging
Relay 2 menu
- added ability to use the second relay
Alarm
mode: the relay will switch when one or more batteries signal an alarm, or when the SOC drops belowMinimum SOC (unless grid fails)
Connect Load
mode: the relay will switch when excess power exceedsConnect load treshold (excess power)
- added
Relay 2 Polarity
: the relay can be configured to beNormally Open
orNormally Closed
- added
Debounce Time
: the relay will switch only when the trigger condition (alarm or excess power) is present for more than the configured time. This allows for avoiding short transitory states (false positives) and prevents the relay from relentlessly switching.
System Overview Screen
- added label that displays the current
Charging State
- added battery temperature inside the battery widget
Charging states
Heating
: The batteries are being heated, the system is not operational.Optimize self-consumption
: The default state. The system is trying to acheive the energy flow from/to the grid configured inGrid setpoint
.Forced EOC
: The system is performing a full charge of the batteries. This can be triggered manually, or it will happen automatically when the batteries haven't been fully charged for more than a week.Hold min SOC
: The system is throttling discharge, or charging with low power in order to prevent the SOC from dropping belowMinimum SOC (unless grid fails)
Charge to min SOC
: The system is charging the batteries in order to reachMinimum SOC (unless grid fails)
Bridge grid blackout
: The grid has lost power (blackout). The system is feeding the loads connected to AC-out by discharging the batteries.Limit discharge power
: The battery discharge power is being throttled. By settingLimit the discharge power
, discharge power is limited to a chosen set-value.Limit charge power
: The battery charge power is being throttled. By settingLimit the charge power
, charge power is limited to a chosen set-value.Scheduled charge
: The battery is charging when a planned charge (done using the optionScheduled charging
) is due.No grid meter available
: The system isn't recognizing an installed grid meter. The system will attempt to charge the battery.
Controller
- added new controller that is optimized for salt batteries. The standard Victron controller is geared toward Lead-Acid batteries,it cannot efficiently deal with salt batteries.
- added ability to limit power by the effective current and voltage limits of the battery, increasing the available discharge power by 10-20%
- added
Hold min SOC
mode that throttles discharge on low SOC conditions and compensates for heat loss. - added
Forced EOC
mode that forces batteries to be fully charged, at least once per week, but no more than necessary. - added
Charge to min SOC
mode that forces batteries to be charged till reaching the min SOC, if there was a blackout that led the SOC to fall under the minimum value. - added
Bridge grid blackout
mode that operates the loads using battery power, when a blackout happens. Priority goes to the critical loads. - added
Limit discharge power
mode that limits the discharge power of the battery and depends on the grid if more power is needed than the limit. - added
Limit charge power
mode that limits the charge power of the battery, making it charge with less power over a more period of time. - added
Scheduled charge
mode that allows the user to plan a charge beforehead. Up to 5 different charge plans are available at the same time in theScheduled charge
inCharging Strategy
menu. - added
No grid meter available
mode that detects if a grid meter isn't recognised or connected properly.