745 B
745 B
# Optimize Self-Consumption -> Limit Discharge Power
Initial State: Optimize Self-Consumption
Target State: Limit Discharge Power
Test Procedure
- The system is brought to the
Optimize Self-Consumption
state by settingMin SOC
lower than the current SOC. Grid setpoint
is set to 0W.- The
Limit Discharge Power
option is activated and theMaximum Discharge Power
is set to 1000W. - A load of 2000W or more is connected to the system.
Expected Outcome
As soon as the load is connected, the battery state changes into the Limit Discharge Power
state and discharges with a maximum power of 1000W(+/-50W).
The rest of the load is supplied by the grid.
Tested Outcome
The systen reacted as expected.