# Forced EOC -> Optimize Self-Consumption (charging)
Initial State: Forced EOC
Target State: Optimize Self-Consumption
Test Procedure
SOC
should be 98% or below- A production surplus is simulated by setting the
Grid setpoint
to a positive value: 2000W - The system is brought to the
Forced EOC
state usingForce charge now
in the gui. - Wait until the system changes to
Optimize Self-Consumption
Expected Outcome
- The system charges the battery to EOC in the
Forced EOC
state. - charging power decreases as SOC approaches 100%
- the system changes into
Optimize Self-Consumption
- the system continues to charge with very low power <100W or discharges with very low power <100W
Time to forced full charge
displayed on the gui is 6d 18h +-1h
Tested Outcome
The system reacted as expected and switched to Optimize Self-Consumption
when the battery is fully charged and having
100% SOC. The system is continuously charging with a power of ~3W. Time to forced full charge
is correctly displayed and
gets restarted or stays the same (6d 18h) as long as the battery is in charge mode.